Team Shieldworkz
Cyber-informed engineering (CIE) starts from that question. Instead of only trying to keep attackers out, it asks engineers to make sure that even a successful attacker cannot cause the outcomes the plant cannot live with: an unsafe process condition, damaged equipment, a long outage, or a release into the environment.
This matters more than it did a year ago. The newest SANS industrial survey shows incidents climbing sharply, detection slowing, and very few sites able to confirm that they could run safely without centralized control. At the same time, the U.S. national laboratories have been publishing a steady stream of practical CIE material aimed at the people who actually design and run plants, not only at security teams.
This Blog explains what cyber-informed engineering is, what has changed recently, how the 12 principles translate to plant floor decisions, and how to start without redesigning your whole facility.
Key takeaways
Cyber-informed engineering applies engineering judgment, not just security tools, to limit what a cyber compromise can physically do.
One in three respondents in the latest SANS ICS/OT survey reported an incident in the past 12 months, the largest one-year jump the survey has recorded.
Only 15% of respondents said they could sustain critical processes in manual mode for more than 48 hours, and 40% could not say either way.
CIE is not a replacement for IEC 62443, NIST or NERC CIP. It fills the gap those frameworks leave: consequences that should be impossible by design.
You can start with one process, one consequence and one engineered control. No multi-year program is needed to see value.
What is cyber-informed engineering?
Cyber-informed engineering is a framework that integrates cybersecurity considerations into the engineering lifecycle of physical systems, from concept and design through operation and retirement. It was developed by the U.S. Department of Energy's national laboratories, led by Idaho National Laboratory (INL) with partner laboratories, and is sponsored by DOE's Office of Cybersecurity, Energy Security, and Emergency Response (CESER).
The core idea is simple. Traditional cybersecurity protects the digital system. Traditional engineering protects the physical process. CIE connects the two by asking engineers to use physical, mechanical and procedural controls to bound the damage a cyber event can do. In DOE's own framing, CIE relies on engineering design to provide deterministic controls that reduce the damage potential of an attack.
A useful way to remember it:
Cybersecurity asks: how do we stop the attacker from getting in?
Safety engineering asks: how do we keep the process safe when something fails?
Cyber-informed engineering asks: how do we make sure a deliberate, intelligent attacker cannot cause the failure we most fear, even if they get in?
That last point is what separates CIE from classic safety work. A safety system is designed around random failures. An adversary can pick the moment, combine failures, and manipulate the very systems that are supposed to protect you.
Where CIE came from
The concept grew out of INL's Consequence-driven Cyber-informed Engineering (CCE) work, which helped asset owners identify their highest-consequence events and the paths an attacker would need to cause them. In June 2022, DOE published the Congressionally directed National Cyber-Informed Engineering Strategy. It is organized around five pillars: Awareness, Education, Development, Current Infrastructure and Future Infrastructure.
In August 2023, DOE released the CIE Implementation Guide, which sets out the 12 CIE principles and the questions engineering teams should ask at each lifecycle stage. It has since been developed into a web-based CIE Analysis Tool, and the program has continued to add case studies and sector-specific material.

Why CIE is getting attention now: what the latest data says
The SANS 2026 State of ICS/OT Security Survey, published in November, drew roughly 700 respondents and pointed to a growing role for CIE alongside a push for resilience-focused controls. The findings read like an argument for designing consequences out rather than detecting them faster:
34% of respondents had an ICS/OT cyber incident in the past 12 months. Coverage of the report describes this as about 1.7 times the prior-year rate and the largest single-year increase SANS has recorded.
72% of those incidents caused facility or system downtime.
Safety impact is rising. The share of respondents reporting an incident that affected safety increased from 8% to 13%.
Detection got slower for the first time in the survey's history. Only 41% of incidents were caught within 24 hours, down from more than half in the two previous years.
Visibility is still thin. Just 13% report full IT/OT visibility across the ICS Cyber Kill Chain, and budget is the most common barrier to expanding detection.
Manual fallback is unproven. Only 15% are fully capable of running critical processes in manual mode for more than 48 hours without centralized SCADA or DCS control. Another 34% are partially capable. 40% do not know.
Leaders and operators disagree. In the leadership module, every responding security leader expected their plants to keep running through a full IT compromise, yet the practitioners who would actually run manual operations were far less certain. SANS notes the leadership sample is smaller, so treat it as a signal rather than a verdict.
Dependencies are fragile. 68% say losing one or two key people would delay or severely risk ICS/OT security and incident response, and only 20% report a fully functional supply chain cyber risk management program.
Testing pays off. Organizations that test resilience plans at least annually and fold ICS/OT into business continuity and disaster recovery were more likely to expect to recover their most critical facility within a day (46% versus 27% overall). These are self-assessments, but the gap is notable.
Read together, these numbers say something uncomfortable. Detection is improving in tooling terms (dedicated ICS/OT detection platforms found more incidents than any other method), yet outcomes are getting worse. Detection tells you something is wrong. It does not guarantee the plant stays safe and running while you respond. That is exactly the gap cyber-informed engineering is built to close.
The latest CIE developments plant teams should know about
CIE has moved quickly from concept to toolkit. Here is what has been released or announced recently:
CIE Guide for States (November 2025). INL published guidance for state energy offices and public utility commissions, including use cases around grants, training, interconnection and allow lists. It shows how CIE can be written into funding and procurement decisions.
Integrating CIE into Process Automation (September 2025). INL authors analyzed how CIE principles apply to process automation systems, explicitly noting that automation brings efficiency and new cyber risk together.
Adapting Traditional Hazards Analysis to Cyber Risks (September 2025). This INL report compares conventional hazard analysis with CIE and maps alignment to safety standards such as IEC 61508 and IEC 61511. For plant engineers, it is the most direct bridge between HAZOP-style thinking and cyber.
U.S. standards and regulation risk mapping (February 2026). An INL report that maps the landscape of federal, state, voluntary and utility-driven standards for digital energy systems, pointing out that some assets sit outside mandatory rules such as NERC CIP.
CIE Standards Development Organization Quick Start Guide (May 2026). A national laboratory guide showing how standards bodies can interpret the 12 principles when writing and revising standards.
Sector workbooks. INL has released guided exercises for water utilities, substations, ADMS and microgrids, each applying the 12 principles through consequence analysis, engineered controls and design exercises.
A growing education pipeline. More than 22 universities have incorporated CIE into engineering courses and certificates, and INL launched a short-lesson CIE School video series on the 12 principles in October.
Standards alignment. DOE has noted that the International Society of Automation is using the Securing Energy Infrastructure Executive Task Force body of work to develop profiles for the ISA/IEC 62443 series.
The direction is clear. CIE is being embedded in standards, grants, curricula and sector playbooks, which means plant owners will increasingly be asked how they have applied it, whether by regulators, insurers, customers or boards.
The 12 CIE principles, translated for the plant floor
The principles come from the DOE CIE Implementation Guide. Each one is paired here with a question a plant engineer can actually answer.
Consequence-focused design. What are the few outcomes we cannot accept, and which functions could cause them? Start here. Everything else follows.
Engineered controls. Where can a physical or mechanical control (a relief valve, an interlock, an analog limit) override the digital layer entirely?
Secure information architecture. How does data flow, and is each flow necessary? Can sensitive control paths be one-way or isolated?
Design simplification. What can we remove? Every unnecessary function, protocol, remote path and vendor connection is attack surface.
Layered defenses. If one layer fails, is the next independent, or does it share the same credentials, network and software?
Active defense. Can our people monitor, hunt and respond in the OT environment, and do they know what normal looks like?
Interdependency evaluation. What does this system rely on (power, telecoms, cloud, identity, a vendor) that an attacker could pull on?
Digital asset awareness. Do we know every digital device that can influence the process, including the ones nobody documented?
Cyber-secure supply chain controls. Can we trust and verify what vendors, integrators and components bring into the plant?
Planned resilience. What is the fallback, and has anyone rehearsed it? This is where the 15% manual-operations figure becomes personal.
Engineering information control. Who can see drawings, logic, network maps and configs, and how well are they protected? Attackers need engineering knowledge to cause precise consequences.
Organizational culture. Do engineering, operations, safety and security share the goal, or do they work from different priorities?
CIE vs. traditional OT cybersecurity: how they differ
Traditional OT security | Cyber-informed engineering | |
Starting point | Assets, vulnerabilities, threats | Unacceptable consequences |
Main controls | Network segmentation, monitoring, patching, access control | Physical limits, simplification, independent layers, rehearsed fallbacks |
Owner | Security / IT-OT team | Engineering, operations and security together |
Assumption | We can detect and block most attacks | A determined attacker may still get in |
Time in lifecycle | Mostly operate and maintain | Concept, design, build, operate and retire |
The two are complements. Monitoring and segmentation reduce the chance of an attacker reaching the process. CIE reduces what happens if they do.
A practical way to apply CIE in an existing plant
You do not need a greenfield project. Most CIE value for operating plants comes from a focused exercise on the highest-consequence functions. A workable approach:
Step 1: Define the consequences you cannot accept
Gather operations, safety, engineering, maintenance and security in one room. List the top five to ten events that would be unacceptable: loss of containment, equipment damage that takes months to replace, a prolonged production loss, contamination of product or water, a safety incident. Rank them by severity and recovery time.
Step 2: Identify the functions that could cause them
For each consequence, ask which control functions, setpoints, sequences and permissives would have to be manipulated. Trace these to the digital components involved: PLCs, DCS controllers, safety systems, HMIs, historians, remote access paths, vendor tools.
Step 3: Map how an attacker could reach and abuse those functions
Do this as an engineer, not as a scanner. Where does the logic live? Who can change it? Which network paths, accounts, removable media and vendor connections lead to it? Which engineering workstation is the quiet single point of compromise?
Step 4: Add engineered controls that do not depend on the compromised layer
This is the heart of CIE. Typical examples include:
Mechanical relief and overspeed protection that act regardless of controller state
Hardware interlocks and hardwired trips independent of the main control network
Physical limits on actuators, rate-of-change limiters and range clamps enforced in separate hardware
Unidirectional gateways or hardware-enforced one-way paths where data only needs to flow out
Analog or local indication that operators can trust if the HMI cannot be trusted
Physical key switches and local manual overrides for the most critical actions
Removing remote write access from critical loops entirely
Step 5: Prove the fallback works
Test manual operation with the operators who would perform it, not just the engineers who wrote the procedure. Time it. Find what breaks: missing documentation, unlabeled valves, staffing gaps, or dependence on a screen. The SANS data suggests most sites have never answered this question with evidence.
Step 6: Make it part of the engineering process
Add CIE questions to management of change, front-end engineering design, vendor selection and commissioning checklists. If CIE only exists as a one-time workshop, it will decay.
Where CIE fits with the standards you already use
IEC 62443: Gives you zones, conduits, security levels and secure product and development lifecycle requirements. CIE helps you decide which consequences deserve the strongest zones and which functions should never rely on a networked control alone.
IEC 61511 / 61508 and HAZOP/LOPA: Safety lifecycle work already identifies hazards and protection layers. The recent INL report on adapting hazards analysis shows how to add a deliberate-attacker lens, because independence assumptions that hold for random faults may not hold for an adversary.
NIST SP 800-82 and NIST CSF: Provide control catalogs and program structure. CIE tells you where to invest first.
NERC CIP: Mandatory for the bulk electric system, but it does not cover all digital assets in energy. CIE can fill the gaps through voluntary design practices.
Common pitfalls
Treating CIE as a security-team project. It fails without engineers, operators and safety leads in the room.
Assuming your safety system is cyber-proof. Safety instrumented systems have been targeted in real attacks, notably the Triton malware incident that went after safety controllers. Independence must hold against a thinking adversary.
Confusing a manual procedure with a manual capability. A binder on a shelf is not a tested fallback.
Over-trusting the leadership view. The SANS findings show a confidence gap between leaders and operators. Ask the people who run the process.
Ignoring engineering data. Network diagrams, logic backups and vendor manuals are exactly what an attacker uses to craft a precise consequence.
Overlooking dependencies. The survey suggests a majority of respondents would be down within a year if their primary automation vendor disappeared, and many rely on a few key people.
Your first 90 days
Days 1 to 30: Run a consequence workshop for one critical process. Document the top consequences and the functions behind them.
Days 31 to 60: Trace digital dependencies for those functions. Identify two or three candidate engineered controls and check feasibility and cost with your engineering team.
Days 61 to 90: Run a timed manual operations exercise with operators. Fix what fails. Add CIE questions to your management of change process.
For teams that want structured exercises, the INL sector workbooks (water, substations, ADMS and microgrids) are a good starting framework, and the CIE Community of Practice runs working groups for standards, education and implementation.
How Shieldworkz helps plants put CIE into practice
Shieldworkz is an end-to-end industrial OT cybersecurity company. We cover the full stack: services, platform and solutions for SCADA, OT and IoT environments. Cyber-informed engineering works best when it sits alongside the controls that make attacks harder to start and faster to spot. Our teams support plants with:
Consequence and risk assessments that rank critical functions and attack paths with your engineers
OT asset visibility and monitoring to cover the digital asset awareness and active defense principles
Architecture and segmentation design aligned with IEC 62443 zones and conduits
Incident response and recovery readiness, including exercises that involve operators and engineering recovery of PLCs, RTUs and HMIs
Secure remote access and supply chain controls to reduce vendor and third-party exposure
If you are planning a new build, a retrofit or a resilience review and want to apply CIE in practice, talk to the Shieldworkz team about a consequence-driven assessment for your site.
Frequently asked questions
What is cyber-informed engineering in simple terms? It is an approach where engineers design and modify systems so that a cyber compromise cannot cause the worst physical outcomes, using physical and procedural controls as well as digital security.
Who developed cyber-informed engineering? The U.S. Department of Energy's national laboratories, led by Idaho National Laboratory with partner laboratories, under DOE CESER sponsorship. The national strategy was published in June 2022 and the Implementation Guide in August 2023.
How is CIE different from IEC 62443? IEC 62443 is a standard series defining security requirements, zones, conduits and lifecycle practices. CIE is a design philosophy that prioritizes consequences and uses engineering controls to limit them. Used together, CIE tells you where to focus, and 62443 helps you structure how to secure it.
Is CIE only for the energy sector? No. It started with energy, but the principles apply to any environment where digital systems influence physical processes, including water, manufacturing, chemicals, oil and gas, and transport. INL has published water and microgrid workbooks, and a process automation paper.
Can CIE be applied to existing plants? Yes. Consequence prioritization, engineered controls, simplification and rehearsed manual operation can all be added to brownfield sites, usually starting with one critical process.
What is an example of an engineered control? A mechanical relief valve, a hardwired overspeed trip, or a hardware-enforced limit that works regardless of what the controller or network says.
How long does it take to start? A first consequence workshop can be done in days. The longer effort is embedding CIE into design, change management and procurement.
Conclusion
The latest industry data shows more incidents, slower detection and thin confidence in manual fallbacks. Hoping to detect every intrusion in time is not a strategy for the processes that matter most. Cyber-informed engineering gives plant managers and engineers a way to take part directly: decide the consequences you will not accept, then build physical and procedural limits that hold even when the digital layer cannot be trusted.
Start small. Pick one process, one consequence and one engineered control, and prove your fallback with the people who would use it. That single exercise will tell you more about your real resilience than another dashboard.
Additional resources
Comprehensive Guide to Network Detection and Response NDR in 2026 here
A downloadable report on the Stryker cyber incident here
Remediation Guides here
OT Security Best Practices and Risk Assessment Guidance here
IEC 62443-based OT/ICS risk assessment checklist for the food and beverage manufacturing sector here
Recibe semanalmente
Recursos y Noticias
Vea cómo nuestras soluciones de seguridad de OT líderes en la industria abordan los desafíos de seguridad críticos
También te puede interesar

Beyond the Breach: Are cyber adversaries actively repositioning inside Western government institutions?

Prayukth K V

Manufacturing Ransomware Statistics 2026: Latest Data on Sectors, Groups and Attack Paths

Team Shieldworkz

SBOM for OT and ICS: What the Latest lwIP Advisories Teach Us About Component Visibility

Team Shieldworkz

OT Tabletop Exercise Scenarios for 2027: 5 Drills Built from Real Incidents

Team Shieldworkz

FERC Approves NERC CIP-015-2: What Changes for Your INSM Program

Team Shieldworkz

What the equinor cyberattack reveals about energy infrastructure resilience

Prayukth K V